| Brand Name: | Hoan |
| Model Number: | JZP-3.0B-SC |
| MOQ: | 4 Pieces |
| Payment Terms: | L/C,D/A,D/P,T/T |
JZP-3.0B-SC is a bonded rubber isolator used to cut structure-borne noise between small building service equipment and the building frame. Rating 3.0 kg nominal load per mount, loaded natural frequency 7 - 15 Hz, body 46 mm diameter by 30 mm height, M4 threaded insert plus a ⌀ 5.5 mm through hole, working temperature -45 to +65 ℃, shock rating 100 G for 12 pulses. Recommended working frequency 15 - 50 Hz, qualification sweep range 5 - 50 Hz. Minimum order quantity 4 pieces, so a single fan coil can be validated before the building package is released.
| Model | JZP-3.0B-SC |
| Product | Rubber shock absorber / vibration isolator for building services |
| Function | Breaks the rigid path that carries structure-borne noise |
| Nominal load | 3.0 kg per mount |
| Loaded natural frequency | 7 - 15 Hz |
| Recommended working frequency | 15 - 50 Hz |
| Qualification sweep range | 5 - 50 Hz (scan only) |
| Envelope | D 46 mm × H 30 mm |
| Mounting | M4 threaded insert + ⌀ 5.5 mm through hole |
| Minimum order quantity | 4 pieces with rapid prototype tooling |
A fan coil, a small air handling unit, a circulation pump or a duct bracket makes very little noise in its own casing. The noise appears two floors away, because vibration travels through steel and concrete with little loss and re-radiates as low frequency hum from floors, ceilings and partitions. Fitting an elastic element between the equipment and the structure interrupts that path. The JZP-3.0B-SC is that element: a bonded rubber body sized for 3.0 kg per support, in a 46 mm diameter by 30 mm high envelope that fits inside equipment rooms where a spring hanger cannot go.
| Parameter | Value | Unit | Tolerance | Condition under which the value is stated |
|---|---|---|---|---|
| Model | JZP-3.0B-SC | - | - | Marking on the part and on the carton |
| Nominal vertical load | 3.0 | kg | nominal rating | Static load, 23 ℃, rigid base, 24 h settling time |
| Static displacement at nominal load | ≤ 0.3 | mm | upper limit | Vertical direction, 23 ℃, measured from free height. This is a ceiling, not the design deflection |
| Natural frequency, loaded | 7 - 15 | Hz | band | Nominal 3.0 kg mass, sine sweep, single vertical axis |
| Resonance reference, unloaded series sheet | 41.5 ± 5 | Hz | ± 5 | Unloaded sweep fixture; value published for the JZP-B-SC family as a whole |
| Recommended working frequency | 15 - 50 | Hz | design band | Isolation region above √2 × loaded natural frequency |
| Qualification sweep range | 5 - 50 | Hz | scan window | Sine sweep 1 oct/min, 3 axes, rigid fixture - scan only |
| Transmissibility in isolation region | ≤ 0.2 | ratio | maximum | From twice the loaded natural frequency upward, vertical axis |
| Shock resistance | 100 G / 12 pulses | G, cycles | series rating | Half-sine pulse on shock machine, 3 axes, after 4 h soak at -45 ℃ and at +65 ℃ |
| Working temperature | -45 to +65 | ℃ | range | Static and dynamic performance quoted inside this window only |
| Body diameter D | 46 | mm | ± 0.5 | Caliper, 3 measuring points, 23 ℃ |
| Overall height H | 30 | mm | ± 1 | Free height, before preload |
| Rubber body height h | 21 | mm | ± 0.5 | Rubber section only, threaded insert excluded |
| Hole pitch A | 40 | mm | ± 0.2 | Centre to centre on the base pattern |
| Base width B | 50 | mm | ± 0.5 | Across flats |
| Threaded insert d | M4 | - | 6H | Thread gauge inspection |
| Through hole d2 | ⌀ 5.5 | mm | +0.2 / 0 | Pin gauge inspection |
| Corner radius R | 5 | mm | drawing value | Reference dimension |
| Service life reference | 8 | year | reference | Sheltered indoor installation, inside rated load and temperature |
| Model | D (mm) | H±1 (mm) | h (mm) | A±0.2 (mm) | B (mm) | d | d2 | R |
| JZP-3.0B-SC | 46 | 30 | 21 | 40 | 50 | M4 | ⌀ 5.5 | 5 |
Frequency values are deliberately separated - please read both lines:
1. Recommended working frequency: 15 - 50 Hz. This is the band where the mount actually isolates, because effective isolation only begins above √2 times the loaded natural frequency. Specify this band when the equipment excitation sits inside it.
2. Test sweep range: 5 - 50 Hz. This is the qualification scan used to measure the curve (sine sweep, 1 oct/min, three axes). It is a laboratory scan window, not a working range. Below roughly 10 Hz the mount amplifies instead of isolating.
3. Loaded natural frequency: 7 - 15 Hz, measured with the nominal 3.0 kg mass. Series resonance reference: 41.5 ± 5 Hz, quoted on the unloaded series sheet. The two numbers describe different test states and must not be mixed when sizing.
Send the equipment mass, the fan or pump speed, the hanger spacing and the mounting detail, and we will confirm the number of JZP-3.0B-SC mounts needed and whether the excitation frequency falls inside the 15 - 50 Hz working band. Four piece minimum orders and rapid prototype tooling let a single riser or plant room be measured before the building package is released.